This article is about the requirements to connect a Wattsense Tower/Bridge to a BMS.
Below the information needed to connect the Wattsense Tower/Bridge with an existing BMS :
| R = Required - O = Optional - N/A = Not Applicable - (*) = See remarks | Checklist | Remarks | ||
| Document | ||||
| BMS network overview | R | It helps to identify the best location of the Box | ||
| Connectivity | ||||
| GSM/3G/4G Signal quality test | R | Not Filled | As indication, use your mobile phone as reference: • Write down the network carrier used for the test • Check the number of network bar of your mobile phone • Check if you can access website smoothly |
|
| Only applicable for IP network | ||||
| Assign IP address and netmask for the Box | R* | (*) Check with the IT manager of the building to gather these informations | ||
| Internet access via ethernet | O* | (*) Check with the IT manager of the building to obtain the gateway IP address | ||
| Protocol used on the BMS primary network | ||||
| BACnet | ||||
| IP (Ethernet/RJ45) |
||||
| BACnet port (UDP port) | R | • IP : Default UDP port is 47808 (0xBAC0) | ||
| BOX should be on the same network as BBMD | R | |||
| Communication configuration (Baud rate) |
N/A | (*) MS/TP: Check with your Wattsense customer support contact | ||
| Modbus | ||||
| IP (Ethernet/RJ45) |
RTU (RS485) |
|||
| Slave address of all equipment | * | R | (*) This is required when Modbus TCP/IP <==> RTU gateway is used (e.g Schneider EGX 150) | |
| IP address and UDP ports of all equipment | R | N/A | Default UDP port is 502 | |
| Network communication configuration | N/A | R | Obtain Baud rate/Parity/Data bit/Stop bit of each Modbus network (Contact your technical team responsible for the BMS) | |
| Modbus register list | O | O | • Required information for the collection of data. Please send via the support contact email: • A list in Xls, CSV, or text file format of the specific data points (properties) you wish to recuperate. - Name of the variables - Register address - Data format - Access type - Modbus function used |
|
For more information, feel free to contact us here.