browse
Description of the changes about to impact the Bridge
|
Bridge with Ethernet connection + SIM card*
|
Bridge without Ethernet connection (only SIM card)
|
||
Now | After the change | Now | After the change | |
Push a configuration to the box
|
Data uplink MUST be activated | NO data uplink activation required | Data uplink MUST be activated | NO data uplink activation required |
See properties values in the console
|
Data uplink MUST be activated | same | Data uplink MUST be activated | same |
Redirection to a gateway (MQTT Modbus, BACnet)
|
The gateway is on a local IP network: - Data go through ethernet The gateway is on a remote IP server: - Cellular when data uplink activated - Ethernet otherwise |
Data always go through ethernet | The data are redirected only when the data uplink is activated | Not supported (no redirection) |
Access to the box from the Wattsense servers
|
If the Wattsense servers can be reached: - Permanent connection Otherwise: - No permanent connection - One-off connection with the box through text messages |
Permanent connection | - No permanent connection - One-off connection with the box through text messages |
Permanent connection |
Logs/events
|
- Data uplink MUST be activated - Send all queued events |
Default: - Send only critical events (ex.: application start) Data uplink enabled: - Send all events |
- Data uplink MUST be activated - Send all queued events |
Default: - Send only critical events (ex.: application start) Data uplink enabled: - Send all events |
Time interval between two readings
|
60s minimum between two readings for properties configured as LOCAL whatever the gateway (till the gateway server can be reached through the ethernet connection) 600s minimum for properties configured as REMOTE |
same | Same as on the left, but the redirection to a gateway requires an ethernet connection | same |
Status & color | - ONLINE but not sending data - Yellow - Data uplink enabled: ONLINE - GREEN |
same | - OFFLINE - Red - Data uplink enabled: ONLINE - GREEN |
- ONLINE - Yellow - Data uplink enabled: ONLINE - GREEN - OFFLINE if the cellular signal strenght is not strong enough - RED |
* if the cellular connection is not strong enough to communicate with the Wattsense servers (meaning that the box can't get an IP address through the cellular connection), the ethernet connection, when available, is used. When both are available, the cellular connection will have the priority.
As a reminder and for information, the same grid for the Tower:
|
Tower with Ethernet connection + SIM card*
|
Tower without Ethernet connection (only SIM card)
|
||
Now | After the change | Now | After the change | |
Push a configuration to the box
|
/ | / | / | / |
See properties values in the console
|
/ | / | / | / |
Redirection to a gateway (MQTT Modbus, BACnet)
|
The gateway is on a local IP network: - Data go through ethernet The gateway is on a remote IP server: - Cellular |
same | Via the cellular connection | same |
Access to the box from the Wattsense servers
|
/ | / | / | / |
Logs/events
|
/ | / | / | / |
Time interval between two readings
|
60s minimum between two readings for properties configured as LOCAL and not redirected to a MQTT gateway (BACnet and Modbus only) 600s minimum otherwise |
same | 60s minimum between two readings for properties configured as LOCAL and not redirected to a MQTT gateway (BACnet and Modbus only) 600s minimum otherwise |
same |
Status & color | / | / | / | / |
Comments
0 comments
Article is closed for comments.