This topic will give you some tips for troubleshooting a LON IP setup:
- Make sure the Wattsense Box has a static IP address configured.
- Go to Configuration -> Connectors (select the appropriate Ethernet port)
- Connect to the LON configured server and check the IP address of the Box is registered to it.
- The port number MUST match the one set up in the configured server of the LON router (e.g., L-IP).
- Check the domain ID and subnet ID correspond to the ones used by the backbone channel (i.e. main Ethernet channel).

- Backbone channel

- Check the Node Id of the Box is unique on that specific subnet
- If all the above checked were made:
- Add the equipment and a LON variable
- Send the configuration to the Box
If you have any problem, please do not hesitate to contact us: Wattsense Support