This article is about the requirements to connect a Wattsense Tower/Bridge to a BMS.
Below the information needed to connect the Wattsense Tower/Bridge with an existing BMS :
R = Required - O = Optional - N/A = Not Applicable - (*) = See remarks | Checklist | Remarks | ||
Document | ||||
BMS network overview | R | It helps to identify the best location of the Box | ||
Connectivity | ||||
GSM/3G/4G Signal quality test | R | Not Filled | As indication, use your mobile phone as reference: • Write down the network carrier used for the test • Check the number of network bar of your mobile phone • Check if you can access website smoothly |
|
Only applicable for IP network | ||||
Assign IP address and netmask for the Box | R* | (*) Check with the IT manager of the building to gather these informations | ||
Internet access via ethernet | O* | (*) Check with the IT manager of the building to obtain the gateway IP address | ||
Protocol used on the BMS primary network | ||||
LonWorks | ||||
IP (Ethernet/RJ45) |
||||
Export of LNS database in NLC file extension or archive format | R | Generate NLC file of the LNS database using the LNS management tool software. (e.g NL220, Tools--->Export NLC) | ||
Ensure all data points are available on the lonworks | R | Some manufacturers uses on top of LON newtork a proprietary protocol which limits the number of data points available for a third party application | ||
IP address of each IP-852 router | R* | (*) Check with your Wattsense customer support contact | ||
Login / Password and configuration server/client ports of IP-852 router | R | Default Loytec L-IP login/password: Admin/loytec4u | ||
XIF files of each model of equipment | N/A | (*) XIF files are not availabe check with your Wattsense customer support contact | ||
BACnet | ||||
IP (Ethernet/RJ45) |
||||
BACnet port (UDP port) | R | • IP : Default UDP port is 47808 (0xBAC0) | ||
BOX should be on the same network as BBMD | R | |||
Communication configuration (Baud rate) |
N/A | (*) MS/TP: Check with your Wattsense customer support contact | ||
Modbus | ||||
IP (Ethernet/RJ45) |
RTU (RS485) |
|||
Slave address of all equipment | * | R | (*) This is required when Modbus TCP/IP <==> RTU gateway is used (e.g Schneider EGX 150) | |
IP address and UDP ports of all equipment | R | N/A | Default UDP port is 502 | |
Network communication configuration | N/A | R | Obtain Baud rate/Parity/Data bit/Stop bit of each Modbus network (Contact your technical team responsible for the BMS) | |
Modbus register list | O | O | • Required information for the collection of data. Please send via the support contact email: • A list in Xls, CSV, or text file format of the specific data points (properties) you wish to recuperate. - Name of the variables - Register address - Data format - Access type - Modbus function used |
For more information, feel free to contact us here.