This article explains the mapping between different protocols.
OUTPUT (Server) | ||||
---|---|---|---|---|
INPUT (Client) | MQTT | BACNET | MODBUS TCP/IP | |
Lorawan | RW | RW* | RW | |
Modbus RS485 | RW | RW | R | |
Diematic | RW | RW | - | |
M-Bus | R | R | R | |
LPB | RW | RW | - | |
KNX | RW | R | RW |
Device can be used as client, for this please check the mapping below :
OUTPUT (Server) | ||||
---|---|---|---|---|
INPUT (Client) | MQTT | BACNET | MODBUS TCP/IP | |
Modbus IP | RW | R | RW | |
Bacnet IP | RW | - | RW** |
* To send a downlink from a BACnet equipment to a LoRaWAN device, the encoding must be UTF-8 ** For Modbus TCP/IP Read checked : Binary Input/Output/Value => Coil/flag ** For Modbus TCP/IP Write checked: Binary Output <= holding register/uint16 and int16 |